UL LISTED ALARM VALVE

THIS ITEM GOT UL LISTED.

BLUE SEAL ALARM VALVE (BSAV-100):
Brief introduction:
Blue seal "BSAV"alarm valve put the use in spray or foam automatic system of the wet pipe which has two installation way,horizontal and vertical and have got the UL approval.It has comparative advantage in character and practicability.

Usage location:
Install between the force pump system and sprinklers in alarm area.When the fire alarm occur,the former sprinkler burst and start up the valve,convert the flow signal into telecom signal for operate the pump and sent out alarm signal display on the tele exchange.Meanwhile,it can be operate the water motor gong by flow power all its own,without aid of Electrioric power.

Material:

Edit no
Name
Material
1.
 body  ASTM A126 CLASS B
2.
 upper cover  ASTM A126 CLASS B
3.
 plug  STEEL
4.
 seal gasket  E.P.D.M.
5.
 valve seat  ASTM C83600
6.
 valve  ASTM S30400
7.
 valve gasket  E.P.D.M.
8.
 gasket  ASTM S30400
9.
 plug  ASTM S30400
10.
 threat plug  ASTM S30400
11.
 mat  E.P.D.M.(BÅ714 above)
12.
 brass jacket  ASTM S83600
13.
 axes  ASTM S30400
14.
 block ring  ASTM S30400
15.
 spring  ASTM S30400

Design Specification:
Type
BSAV-100
 connect way  Flange
 usage way  horizontal vertical
 maximum pressure  14kgf/cm2
 test pressure  25kgf/cm2
 usage pressure  1.5kgf/cm2゛14kgf/cm2
 minimun current  16 l/min
 pressure loss  3.1m (9.3ft)
 weight  23.3 kgs